Security technology, IT and fiber optics from a single source · Berlin · Germany

Paxton

Integrate and configure PaxLock Pro2 in Net2 and Paxton10

3 minutes reading timeGRAEF Group editorial team

PaxLock Pro2 in Net2 und Paxton10 einbinden und konfigurieren

An electronic door access control system is then useful when it seamlessly integrates into the existing access system. PaxLock Pro2 supports two Paxton platforms: Net2 for classic, PC-based installations and Paxton10 for cloud-based, future-oriented environments. Both offer a completely wireless connection – without cable connection to the door. The GRAEF Group takes on the integration and configuration for companies, authorities and demanding facilities throughout Germany.

Integrating PaxLock Pro2 into Net2

In Net2 environments, PaxLock Pro2 communicates via a Net2 Air Bridge, The device acts as a wireless bridge between the lock and the Net2 PC. Registration is done without any software intervention: a transponder already stored in the database is connected to the reader – PaxLock Pro2 then transmits the data to the Air Bridge. If multiple bridges are within range, the lock automatically selects the one with the strongest signal. After successful pairing, the LED flashes green.

Once the pairing is complete, the configuration opens via the Net2 interface under „Access Points.“ There, you can individually set the release time, duration of release time zones, reader configuration, and output behavior. Paxton’s maximum recommendation for net2 Air Bridges is ten connected PaxLock devices per bridge – a value that should be considered when planning larger installations. For commercial installations in Industrial companies Therefore, it is recommended to carefully plan the bridge positions in public facilities with many doors.

  • Connection via transponder – no manual intervention in the software required
  • Automatic bridge selection based on signal strength
  • Configuration of release time, time zones, and access point names in Net2
  • Up to ten PaxLock devices recommended per Net2 Air Bridge
  • Repositioning: automatic reconnection to the strongest bridge

Integrate PaxLock Pro2 into Paxton10

In Paxton 10 environments, the Paxton10 Wireless Connector Communication. The new PaxLock Pro2 is recognized by displaying a system technician transponder – after that the device appears in the Paxton10 device area as an unassigned fixture. It is assigned to a door object via drag-and-drop. Once assigned, the device is considered to be bound to the system and cannot be taken over by another Paxton10 system.

The administration then runs through „Hardware Management“: Status, battery level, and device assignment are all visible at any time. The initial update after pairing takes about ten minutes – an aspect that should be planned for during commissioning. The GRAEF Group configures Paxton10 installations for different types of buildings, from embassies and administrative buildings to Doctors' offices and clinics.

Bluetooth modes: three variants for different access situations

In Paxton10, it is possible to individually configure how Bluetooth access data is read for each PaxLock Pro2:

  • Transponder mode: Smart access credentials are read as soon as the device is within range
  • Touch to Enter: The user carries the device in the pocket and touches the opening mechanism to open it.
  • Bluetooth deactivated: Smart access data are ignored; only physical transponders are valid

In addition, biometric verification can be activated in Paxton10: The user must unlock their smartphone using a fingerprint or facial recognition before entering. If no screen lock is set up, access is automatically denied. This option significantly increases security – especially when using the device in public places. Security-sensitive objects, where a lost smartphone must not be allowed to access without being locked out.

System requirements for the privacy mode

The privacy mode is disabled by default on both platforms. For Net2, version 7 is required; for Paxton10, SR7 is required. Activation takes place in the device configuration – the fitting itself signals the active mode with a red LED; leaving the room via the interior handle automatically disables it.

Signal quality and frequent installation errors

The most common connection problems do not arise from defective hardware, but from the improper placement of the Air Bridge or the Wireless Connectors. Metal doors and frames attenuate the radio signal, dense materials reduce the range, and shared Wi-Fi networks can interfere when overloaded. Paxton recommends 3 to 4 signal bars for stable connection – if the value remains below this permanently, the bridge should be repositioned.

Other typical error sources: A lock box with too large a handle rotation angle prevents the complete locking mechanism from retracting; a fitting previously connected to another system must first be reset; and unsupported transponder formats do not result in a response from the reader. These points are part of the commissioning test that GRAEF performs as standard after each installation.

If you Paxton products If you would like to use our system in your facility or expand an existing system, the GRAEF Group supports the entire process – from system selection to the final configuration. You can find more information about our working methods on the page. About us. For an initial assessment of your project, our team is available via Planning and consulting available.

Peter Gräf, Gründer der GRAEF Gruppe

GRAEF Group editorial team

Contributions from the practical experience of our installers, project managers and software developers. The group is led by founder Peter Gräf, a DGuSV-certified expert in security technology.

Our team
Up
Questions? Chat